7.3 Programmer description
7.3.1 General
A survey of the most important features:
w
Programs: 8 or 16 (dependent of order)
w
Control outputs: 4
w
Segments:16 per program
w
Segment types: - ramp (set-point and time)
- ramp (set-point and gradient)
- hold segment (holding time)
- step segment (with alarm suppression)
- end segment
All segment types can be combined with ”Wait at the end and call operator”
w
Time unit: configurable in hours:minutes or minutes:seconds
w
Maximum segment duration:9999 hours = 1 year 51 days
w
Maximum program duration:16 x 9999 hours=>18years
w
Gradient:0,01°C/h ( /min) to 9999°C/h ( /min)
w
Program name: 8 characters, adjustable via BlueControl software
w
Bandwidth control: bandwidth high and low (b.Lo,b.Hi) limits defininable for
each program
Programmer level
Programmer description 62 KS 90-1p / KS 92-1p
b.Hi
b.Lo
hold segment
step segment
analog track
control track 1
control track 2
control track 3
control track 4
1
24
5
12
13
14
15
16 (8)
16
PRESET
END
PRESET
RESET
START END
program time run off
3
program end