West-control-solutions KS 92-1 Programmer manual Manual do Utilizador Página 23

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 84
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 22
3.6 Manual self-tuning
The optimization aid should be used with units on which the control parameters
shall be set without self-tuning.
For this, the response of process variable x after a step change of correcting vari
-
able y can be used. Frequently, plotting the complete response curve (0 to 100%)
is not possible, because the process must be kept within defined limits. Values T
g
and x
max
(step change from 0 to 100 %) or Dt and Dx (partial step response) can
be used to determine the maximum rate of increase v
max
.
The control parameters can be determined from the values calculated for delay
time T
u
, maximum rate of increase v
max
, control range X
h
and characteristic K ac
-
cording to the formulas given below. Increase Xp, if line-out to the set-point os
-
cillates.
Operation
KS 90-1p / KS 92-1p 23 Manual self-tuning
Tu
Tg
t
x
y
100%
0%
t
Y
h
X
max
{X
{t
y = correcting variable
Y
h
= control range
Tu = delay time (s)
Tg = recovery time (s)
X
max
= maximum process value
V
max
=
Xmax
Tg
=
{
{
x
t
= max. rate of
increase of process value
Vista de página 22
1 2 ... 18 19 20 21 22 23 24 25 26 27 28 ... 83 84

Comentários a estes Manuais

Sem comentários