profiler 8840
Operating manual
English
9499-040-70711
Valid from: 8405
Vista de página 0
1 2 3 4 5 6 ... 89 90

Resumo do Conteúdo

Página 1 - 9499-040-70711

profiler 8840Operating manualEnglish9499-040-70711Valid from: 8405

Página 2 - ATTENTION!

8840 profilerconnecting example:aCAUTION: Using a Limit controller is recommendable in systemswhere overtemperature implies a fire hazard or other ris

Página 3 - Content2

3 Operation3.1 Front viewLED colours:LED 1, 2, 3, 4: yellowBargraph: redother LEDs: redgIn the upper display line, theprocess value is alwaysdisplayed

Página 4 - Technical data 79

3.2 Behaviour after power-onAfter supply voltage switch-on, the unit starts with the operating level.The unit is in the condition which was active bef

Página 5 - 48 (1.89")

3.4 Error list / Maintenance managerWith one or several errors, the extendedoperating level always starts with the error list.Signalling an actual ent

Página 6 - 2.1 Connecting diagram

OperationError list / Maintenance manager 14 8840 profilerNameDescription Reason Possible remedial actionHCAHeating currentalarm (HCA)-Heating current

Página 7 - 2.2 Terminal connection

gSaved alarms (Err-LED is lit) can be acknowledged and deleted with the digitalinput di1/2/3, the è-key or the Ò-key.Configuration, see page 37: ConF

Página 8

ti2 - Integral time 2 (cooling) in [s]r only, unless set to OFFtd2 - Derivative time 2 (cooling) in [s]r only, unless set to OFFt2 - Minimum cycle tim

Página 9

Optimization at the set-point: (see page 18)For optimizing at the set-point, the controller outputs a disturbance variable to theprocess. This is done

Página 10 - Electrical connections

Pulse attempt after start-upCondition: - tunE = 1 and sufficient set-point reserve provided.The controller outputs 0% correcting variable or Y.Lo and

Página 11 - 3.1 Front view

Optimization-at-the-set-point procedure:The controller uses its instantaneous parameters for control to the set-point. Inlined out condition, the cont

Página 12 - Controller

© West Instruments • Printed in GermanyAll rights reserved. No part of this document may bereproduced or published inany form or by any means without

Página 13 - Operation

Optimization at the set-point for 3-point stepping controllerWith 3-point stepping controllers, the pulse attempt can be made with or withoutposition

Página 14

3.5.4 Self-tuning startStart condition:wFor process evaluation, a stable condition is required. Therefore, thecontroller waits until the process has r

Página 15 - 3.5 Self-tuning

3.5.5 Self-tuning cancellationBy the operator:Self-tuning can always be cancelled by the operator. For this, press Ù and Èkey simultaneously.With cont

Página 16 - Self-tuning 16 8840 profiler

3.5.7 Examples for self-tuning attempts(controller inverse, heating or heating/cooling)Start: heating power switched onHeating power Y is switched off

Página 17 - 8840 profiler 17 Self-tuning

3.6 Manual self-tuningThe optimization aid should be used with units on which the control parametersshall be set without self-tuning.For this, the res

Página 18 - Self-tuning 18 8840 profiler

3.7 Second PID parameter setThe process characteristic is frequently affected by various factors such asprocess value, correcting variable and materia

Página 19 - 8840 profiler 19 Self-tuning

3.8 Alarm handlingMax. three alarms can be configured and assigned to the individual outputs.Generally, outputs OuT.1... OuT.6 can be used each for al

Página 20 - Self-tuning 20 8840 profiler

gThe variable to be monitored can be selected seperately for each alarm viaconfigurationThe following variables can be monitored:wprocess valuewcontro

Página 21 - 8840 profiler 21 Self-tuning

3.9 Operating structureAfter supply voltage switch-on, the controller starts with the operating levels.The controller status is as before power off.gP

Página 22 - Self-tuning 22 8840 profiler

4 Configuration level4.1 Configuration survey4.2Adjustment:wThe configuration can be adjusted by means of keys ÈÌ .wTransition to the next configurati

Página 23

KS90-1p 3Content21. Mounting 52. Electrical connections 62.1 Connecting diagram ...62.2 Terminal connection ...73.

Página 24 - 3.6 Manual self-tuning

4.3 Configuration parametersConfiguration levelConfiguration parameters 30 8840 profilerCntrName Value range Description DefaultSP.FnBasic configurati

Página 25 - Formulas

Configuration level8840 profiler 31 Configuration parametersName Value range Description DefaultrnG.L-1999...9999X0 (low limit range of control) 1-100

Página 26 - 3.8 Alarm handling

1 with current and voltage input signals, scaling is required (see chapter 5.3)Configuration levelConfiguration parameters 32 8840 profilerName Value

Página 27

Configuration level8840 profiler 33 Configuration parametersInP.2Name Value range Description DefaultI.FncFunction selection of INP210no function (sub

Página 28 - 3.9 Operating structure

1 with current and voltage input signals, scaling is required (see chapter 5.3)Configuration levelConfiguration parameters 34 8840 profilerName Value

Página 29 - Adjustment:

Configuration level8840 profiler 35 Configuration parametersLimName Value range Description DefaultFnc.1Function of limit 110switched off1measured val

Página 30 - 4.3 Configuration parameters

Configuration levelConfiguration parameters 36 8840 profilerName Value range Description DefaultSrc.2Source of limit 200process value1control deviatio

Página 31 - Configuration level

Configuration level8840 profiler 37 Configuration parametersName Value range Description DefaultHC.ALAlarm heat current function (INP2)00switched off1

Página 32 - (at CAL level)

Configuration levelConfiguration parameters 38 8840 profilerName Value range Description DefaultFAi.2INP2 error signal00not active1activeFAi.3INP3 err

Página 33

Configuration level8840 profiler 39 Configuration parametersName Value range Description DefaultY.2Controller output Y2 (only visible when O.TYP=0)00n

Página 34

4 8840 profiler4.6.7 8840 profiler with measured value output ...554.6.8 Continuous controller with integrated positioner ( Cntr/ C.Fnc = 6 )56

Página 35

Configuration levelConfiguration parameters 40 8840 profilerName Value range Description DefaultCAllOperator call00not active1activeOut.0-1999...9999S

Página 36

Configuration level8840 profiler 41 Configuration parametersName Value range Description DefaultSP.2Switching to second setpoint SP.200no function (sw

Página 37

Configuration levelConfiguration parameters 42 8840 profilerName Value range Description Defaultm.LocBlockage of hand function00no function (switch-ov

Página 38

Configuration level8840 profiler 43 Configuration parametersName Value range Description DefaultfDI3Forcing di3 (only visible with 8800/8840 Configura

Página 39

1 with current and voltage input signals, scaling is required (see chapter 5.3)Configuration levelConfiguration parameters 44 8840 profilerName Value

Página 40

Configuration level8840 profiler 45 Configuration parametersName Value range Description DefaultCDis3Display 3 controller operating level(only visible

Página 41

gResetting the controller configuration to factory setting (Default)r chapter 12.1 (page 85)+8800/8840 Configurator - the engineering tool for the Wes

Página 42

4.4 Set-point processingThe set-point processing structure is shown in the following picture:Set-point gradient / rampTo prevent set-point step change

Página 43

4.5 8840 profiler cooling functionsWith the 8840 profiler , configuration parameter CYCL (ConF/ Cntr/ CYCL)can be used for matching the cycle time of

Página 44

4.6 Configuration examples4.6.1 On-Off controller / Signaller (inverse)ConF/Cntr: SP.Fn = 0 set-point controllerC.Fnc = 0 signaller with one outputC.A

Página 45

1 MountingSafety switch:For access to the safety switch, the controller must be withdrawn from thehousing. Squeeze the top and bottom of the front bez

Página 46

4.6.2 2-point controller (inverse)ConF / Cntr: SP.Fn = 0 set-point controllerC.Fnc = 1 2-point controller (PID)C.Act = 0 inverse action(e.g. heating a

Página 47 - 4.4 Set-point processing

4.6.3 3-point controller (relay & relay)ConF / Cntr: SP.Fn = 0 set-point controllerC.Fnc = 3 3-point controller (2xPID)C.Act = 0 action inverse(e.

Página 48

4.6.4 3-point stepping controller (relay & relay)ConF / Cntr: SP.Fn = 0 set-point controllerC.Fnc = 4 3-point stepping controllerC.Act = 0 inverse

Página 49 - 4.6 Configuration examples

4.6.5 Continuous controller (inverse)ConF / Cntr: SP.Fn = 0 set-point controllerC.Fnc = 1 continuous controller (PID)C.Act = 0 inverse action(e.g. hea

Página 50

4.6.6∆ - Y - Off controller / 2-point controller with pre-contactConF / Cntr: SP.Fn = 0 set-point controllerC.Fnc = 2 ∆ -Y-Off controllerC.Act = 0 inv

Página 51

4.6.7 8840 profiler with measured value outputConF / Out.3 / 4: O.tYP = 1 Out.3/ 4 0...20mA continuous= 2 Out.3/ 4 4...20mA continuous= 3 Out.3/ 4 0..

Página 52

4.6.8 Continuous controller with integrated positioner ( Cntr/ C.Fnc = 6 )This is basically a cascade. A tracking controller with three-point stepping

Página 53

5 Parameter setting level5.1 Parameter surveyAdjustment:wThe parameters can be adjusted by means of keys ÈÌwTransition to the next parameter is by pre

Página 54

5.2 Parameters1 Valid for ConF/ othr/ dP = 0. With dP = 1 / 2 / 3 also 0,1 / 0,01 /0,001 is possible.Parameter setting levelParameters 58 8840 profile

Página 55

1 Valid for ConF/ othr/ dP = 0. With dP = 1 / 2 / 3 also 0,1 / 0,01 /0,001 is possible.Parameter setting level8840 profiler 59 ParametersName Value ra

Página 56

2 Electrical connections2.1 Connecting diagramgDependent of order, the controller is fitted with :wflat-pin terminals 1 x 6,3mm or 2 x 2,8mm to DIN 46

Página 57 - 5.1 Parameter survey

gResetting the controller configuration to factory setting (Default)r chapter 12.1 (page 85)Parameter setting levelParameters 60 8840 profilerName Val

Página 58 - 5.2 Parameters

5.3 Input scalingWhen using current, voltage or resistance signals as input variables for InP.1,InP.2 or/and InP.3 scaling of input and display values

Página 59 - 8840 profiler 59 Parameters

6 Calibration levelMeasured value correction ( CAL) is only visible if ConF / InP.1 / Corr = 1or 2 is chosen.The measured value can be matched in the

Página 60 - Parameters 60 8840 profiler

Offset correction ( ConF/ InP.1 / Corr =1 ):InL.1: The input value of the scaling point is displayed.The operator must wait, until the process is at r

Página 61 - 5.3 Input scaling

2-point correction ( ConF/ InP.1 / Corr = 2):InL.1: The input value of the lower scaling point is displayed.The operator must adjust the lower input v

Página 62 - ( ConF/ InP.1 / Corr = 2 ):

7 Programmer level7.1 Parameter surveySetting:wThe parameters can be set by means of keysIDwTransition to the next parameter is by pressing keyÙ .wAft

Página 63 - ( ConF/ InP.1 / Corr =1 ):

7.2 ParametersProgrammer levelParameters 66 8840 profilerProGName Value Range Description Defaultb.Lo0...9999Bandwidth lower limitOffb.Hi0...9999Bandw

Página 64 - 64 8840 profiler

Programmer level8840 profiler 67 ParametersName Value Range Description DefaulttYPEsegment type 3 (see segment type 1)0SP-1999...9999segment end set-p

Página 65 - 7.1 Parameter survey

7.3 Programmer description7.3.1 GeneralA survey of the most important features:wPrograms: 8 or 16 (dependent of order)wControl outputs: 4wSegments: 16

Página 66 - 7.2 Parameters

7.3.2 Programmer set-up:The instrument is factory-configured as a program controller. The followingsettings must be checked:wSet-point functionFor usi

Página 67 - 8840 profiler 67 Parameters

2.2 Terminal connectionPower supply connection 1See chapter 11 "Technical data"Connection of outputs OUT1/2 2Relay outputs (250V/2A),potenti

Página 68 - 7.3 Programmer description

Programmer parameter setting8(16) programmers with 16 segments each are available to the user. The relevantparameters must be determined in menu ProG

Página 69

7.3.3 OperationProgrammer operation (run/stop, preset und reset) is via front panel, digital inputsor interface (8800/8840 Configurator, superordinate

Página 70 - 1199 1199 1199

7.3.4 Programmer displayProgrammer is in reset and the internal controller set-pointis effective. Segment or program number and OFF aredisplayed (conf

Página 71 - 119.9 1199 1199 1199

7.3.5 Segment typeRamp-segment(time)With a ramp segment (time), the set-point runs linearly fromthe start value (end of previous segment) towards the

Página 72 - 01/12:30

7.3.6 Bandwidth monitoringBandwidth monitoring is valid for allprogram segments. An individualbandwidth can be determined for eachprogram.When leaving

Página 73

8 Special functions8.1 8840 profiler as Modbus masteraThis function is only selectable with 8800/8840 Configurator (engineering tool)!The 8840 profile

Página 74

8.2 LinearizationLinearization for inputs INP1 or INP3Access to table “ Lin” is always with selection of sensor type S.TYP = 18:special thermocouple i

Página 75 - 8 Special functions

9 8800/8840 Configurator8800/8840 Configurator is the projection environment for the correspondingWest controllers. The following 3 versions with grad

Página 76 - 8.2 Linearization

10 VersionsAccessories delivered with the unitOperating manual (if selected by the ordering code)w2 fixing clampswoperating note in 12 languagesAccess

Página 77 - 9 8800/8840 Configurator

11 Technical dataINPUTSPROCESS VALUE INPUT INP1Resolution: > 14 bitsDecimal point: 0 to 3 digits behind thedecimal pointDig. input filter: adjustab

Página 78 - 10 Versions

Connection of output UT9 (option)Supply voltage connection for external energizationConnection of outputs OUT5/6 0 (option)Digital outputs (opto-coupl

Página 79 - Thermocouples

CONTROL INPUTS DI2, DI3 (OPTION)The digital input di2 located on the A-card anddi2 located on the option card are or-linked.Configurable as switch or

Página 80 - T (OPTION)

POWER SUPPLYDependent of order:AC SUPPLYVoltage: 90...260 V ACFrequency: 48...62 HzPower consumption approx. 7,0 VAUNIVERSAL SUPPLY 24 V UCAC voltage:

Página 81 - Technical data

CertificationsUL-approvalElectrical connectionswflat-pin terminals 1 x 6,3mm or 2 x 2,8mm toDIN 46 244 orwscrew terminals for 0,5 to 2,5mm²MountingPan

Página 82

Technical data8840 profiler 83Thermoelementtype Measuring range Accuracy Resolution (Ô)L Fe-CuNi (DIN) -100...900°C -148...1652°F ß 2K 0,1 KJ Fe-CuNi

Página 83

12 Safety hintsThis unit was built and tested in compliance with VDE 0411-1 / EN 61010-1 andwas delivered in safe condition.The unit complies with Eur

Página 84 - 12 Safety hints

MAINTENANCE, REPAIR AND MODIFICATIONThe units do not need particular maintenance.aWarningWhen opening the units, or when removing covers or components

Página 85 - Safety hints

Index0-92-point correction...62AAlarm handling ...26-27BBargraph ...11BlueControl...77Bus interfaceTechnical

Página 86 - ...62

Technical data ...80Output OUT2Configuration ...38Technical data ...80Output OUT3Configuration ...38Technical data ...

Página 87 - 8840 profiler 87

13 NotesNotes88 8840 profiler

Página 88 - 13 Notes

Notes8840 profiler 89

Página 89 - 8840 profiler 89

* Interface description Modbus RTU in speperate manual: see page 78.Electrical connections8840 profiler 9 Terminal connection1345678910111213141517(2)

Página 90

Subject to alterations without noticeWest InstrumentsThe Hyde Business ParkBrightonBN2 4JUUKPrinted in Germany 9499-040-70711 (09/2003)A6